9 | Links 2 Retrofit for GSTC / SETC B+, NHTC, NHRS
Step 2 Wiring the Nortec Links 2 Module
1 Most of the wiring connections for the new Nortec LINKS 2 module will have already been
finished at the factory; however, there are a few connections that will need to be made to
connect the unit the NHTC series humidifier. Refer the LINKs 2 wiring diagram included in
the package for details.
2 Module Power Connections: There will be a wire harness provided that will consist of a red
and blue wire. Both red and blue wires are terminated with a ring terminal.
a The ring terminal of the red wire is to be connected to the 24V side of the transformer
located at the bottom, left of the electrical compartment.
b The ring terminal of the blue wire is to be connected to the ground terminal on the 24V
side of the transformer
3 Humidifier Communication Connection: On the Nortec Links 2 assembly there will be a CAT5
cable with RJ45 connector.
a This connector is to be plugged into the jack on the bottom right side of the humidifier
mainboard.