Modbus
Installation and
Operation Manual
Using Modbus with Nortec
Humidifiers. Includes installation,
operation maintenance and
troubleshooting information.
2560599-D| 05 JUN 2014
Important:
Read and save these instructions. This guide to be left with equipment owner.
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - Operation Manual

Modbus Installation and Operation Manual Using Modbus with Nortec Humidifiers. Includes installation, operation maintenance and

Page 2 - MODEL #

Figure 4: TC Modbus Wiring Diagram Modbus Installation | 7

Page 3 - Contents

Figure 5: MES2 and RH2 Modbus Wiring Diagram 8 |Modbus Installation

Page 4 - Modbus Installation

Figure 6: NHRS Modbus Wiring Diagram Modbus Installation | 9

Page 5 - Wiring Connections

Addressing and Communications Once the humidifier has been wired to the network, control variables must be mapped to allow for control of the humidif

Page 6 - Modbus Installation

Control Signal Setting By default the humidifier is configured operate on a hardwired control signal supplied through the unit terminal strip. This

Page 7 - NH-EL Models

The following points may be mapped for control: Parameter Name Description Modbus Addr. Type Format Range Unit R/W Details Dinput_A1 Write RH or Dem

Page 8 - NHRS Models

SP_Chan_B1 Writes the desired space setpoint for control channel 1 for cylinder B 40008 Holding Register Integer 0 - 95 % Write Use only with NH-E

Page 9 - 6

Fan_ Activate_B Indicates if air handle or furnace is activated for cylinder B 30019 Input Register Integer 0 or 1 - Read 0 = Not Activated 1 = Ac

Page 10 - Modbus Installation

NHTC Electrode Steam Humidifiers After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through th

Page 11 - 8

Control Signal Setting By default the humidifier operation is configured on a hardwired control signal supplied through the unit terminal strip. Th

Page 12 - Modbus Installation

Thank you for choosing Nortec. Proprietary Notice This document and the information disclosed herein are proprietary

Page 13 - Check Mark

Modbus Parameters The NHTC uses the following parameters for communication: Signaling Type EIA-485 Transmission Mode RTU Baud Rate 9600 Data Bits

Page 14

The following points may be mapped for control: Variable Name Description Addr. Type Format Range Unit R/W Details CapLimitCyl1 Sets a manual capaci

Page 15

Set2Cyl2 Writes the desired space setpoint for control channel 2 for cylinder 2 41010 Holding Register Integer 30-95 % Write Use only with NHTC-15

Page 16

Cyl2OpTime Reads operating time for cylinder 2 31213 Input Register Integer 0 - 65535 5 min Read Reads operating time for cylinder 2 (NHTC-150 and N

Page 17

GSTC Gas Fired Steam Humidifiers After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through t

Page 18 - Modbus Installation

To adjust this setting: 1 Press the Menu key to access the menu. 2 When prompted for a password, enter 0335 using the arrow keys. Confirm the pass

Page 19

The following points may be mapped for control: Variable Name Description Addr Type Format Range Unit R/W Additional Details RHDem1 Write RH o

Page 20

InputType Confirms the control type that the humidifier operates on 40007 Input Register Analog 0,1,2,3 - Read 0 = Demand Signal 1 = On/Off Sig

Page 21

SETC Steam Exchange Humidifiers After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through th

Page 22

Control Signal Setting By default the humidifier is configured operate on a hardwired control signal supplied through the unit terminal strip. This

Page 23

Contents 2 Introduction 2 Requirements 2 Wiring Connections 10 Addressing and Communication 10 NH-EL 15 NHTC 21 GSTC 25 SE

Page 24 - Modbus Installation

The following points may be mapped for control: Variable Name Description Addr Type Format Range Unit R/W Additional Details RHDem1 Write RH o

Page 25

NetSensor Confirms the system control type 40226 Input Register Binary 0,1 - Read 0 = Hard wired control signal 1 = Use Modbus to write control si

Page 26

MHTC Evaporative Media Humidifiers After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through

Page 27

Control Signal Setting By default the humidifier is configured operate on a hardwired control signal supplied through the unit terminal strip. This

Page 28 - Modbus Installation

Modbus Parameters The MHTC uses the following parameters for communication: Signaling Type EIA-485 Transmission Mode RTU Baud Rate 9600 (cannot be c

Page 29

NetSensor Switches between hard wired or network control signal 40002 Holding Register Integer 0 or 1 - Write 0 = Wired Analog Sensor/Demand 1 = M

Page 30

MES2 and RH2 Models The default Modbus address for a humidifier is 1. To view or change the unit number: 1 Establish Modbus communications and m

Page 31

The following points may be mapped for control: Variable Name Description Addr Type Format Range Unit R/W Details HumEnable Configures how humidifi

Page 32 - Modbus Installation

Baud Sets the Modbus baud rate 40202 Holding Register Integer 0,1,2 - Write Changes to this variable do not take effect until the humidifier has b

Page 33

ForceReset Resets the controller and restarts in standby. 40007 Holding Register integer 0,255 - Write Write 255 to this register to reset the con

Page 34

CAUTION: Servicing • Disconnect main power before any servicing. • The plumbing and electrical compartments contain high voltage components and

Page 35

Status Displays status of various components. 30107 Input Register Integer 0 - 128 - Read Significant bits: 1 (Bit 0), 2 (Bit 1), 4 (Bit 2), 8 (Bi

Page 36 - MES2 and RH2 Models

CtrlStatus2 Hardware status Port D_E 30110 Input Register Integer 0-32768 - Read Bit 4 - MODBUS Control Active (0 = J26 installed) Bit 9 - FILL (1 =

Page 37

NHRS Electric Steam Humidifiers After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through th

Page 38

Modbus Parameters The NHRS uses the following parameters for communication: Signaling Type EIA-485 Transmission Mode RTU Baud Rate 9600 Data Bits 8

Page 39

The following points may be mapped for control: Variable Name Description Addr Type Format Range Unit R/W Details CapLimit Set a manual capacity re

Page 40

Troubleshooting Problem Resolutions Cannot see/change set point over Modbus. Check control type. Demand type controls use internal algorithms to ge

Page 41

Invalid data Check Modbus addresses for conflicts. Each Modbus device on the network must have a unique address. Devices (humidifiers or otherwise)

Page 42 - Modbus Installation

Figure 7: Humidifier COM port 3 Route the ribbon cable through the punch out on the humidifiers front electrical panel Figure 8: Routing of Rib

Page 43

4 Connect the ribbon cable 20 pin side to the Logic Card. Figure 9: Pin connection for Ribbon cable 5 Configured dipswitch settings according t

Page 44

6 Connect the RJ-11 cable to the corresponding jack on the logic card. Figure 11: RJ-11 Jack Location on Logic Card 7 Mount logic card with nylo

Page 45 - Troubleshooting

Introduction Many Nortec humidifiers feature control boards that include Modbus RTU and can connect to Modbus networks right out of the box. This d

Page 46 - Appendix A

8 Mount the Terminal strip (3 pole) below or above the existing NHRS low voltage terminal strip Figure 13: Low voltage terminal strip on NHRS Humi

Page 47

Warranty Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two y

Page 48 - Modbus Installation

U.S.A. 2700 90th St. Sturtevant, WI 53177 835 Commerce Park Dr. Ogdensburg, NY 13669-2209 CANADA 2740 Fenton Road Ottawa, Ontario K1T 3T7 TEL: 1.

Page 49 - 46

connected to a single chain/bus. The humidifiers should be the same type but do not need to be the same capacity. For example it is not recommended

Page 50 - Modbus Installation

NH-EL Models The NH-EL models use a 3 pole connector on the main processor card for Modbus connection. This 3 pole connector is provided with all NH-

Page 51 - Warranty

NHTC, GSTC, SETC, and MHTC Models The NHTC, GSTC, SETC, and MHTC models use a multifunction RJ45 plug on the mainboard to provide Modbus communicatio

Page 52

Figure 3: NH-EL Modbus Wiring Diagram 6 |Modbus Installation