InputType
Confirms the
control type
that the
humidifier
operates on
40007
Input
Register
Analog 0,1,2,3 - Read
1 = On/Off Signal
2 = RH Sensor
Value (Use
Proportional
Control)
3 = RH Sensor
Value (Use
Proportional-
NetSensor
Confirms the
system control
type
40226
Input
Register
Binary 0,1 - Read
control signal
1 = Use Modbus to
write control signal
Fault
30301
Binary 0,1 - Read
0 = No Fault
1 = Fault Detected
Service
Read service
warning status
30300
Input
Register
Binary 0,1 - Read
Warning
1 = Service
Status
humidification
30302
Input
Register
Binary 0,1 - Read
1 = Active /
Connection
Read
connection
status
40267
Input
Register
Binary 0,1 - Read
Error
1 = Normal
HourOpt
operational
30350
Input
Register
Analog
0 -
Infinity
hrs Read
Displays hours of
operation.
KeepWarm
keepwarm
option status
(enable/disable
30356
Input
Register
Analog 0,1 - Read
Bit0 - KEEPWARM
0 = Disabled
1 = Enabled
3DayDrain
drain option
status
(enable/disable
30356
Input
Register
Analog 0,1 - Read
Bit1 - 3 DAY DRAIN
0 = Disabled
1 = Enabled
output /
30347
Input
Register
Analog 0-100 % Read
percentage of
ServHours
before next
30352
Input
Register
Analog 500-0 hrs Read
remaining until
SecurityLoop
Displays status
of security loop.
30364
Input
Register
Analog 0,1 - Read
of the security loop
on terminals 1 and
2. Loop must be
"closed" for
humidifier to
operate.
0 = Open
24 |Modbus Installation