Nortec Modbus User Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
Cyl2OpTime
Reads
operating
time for
cylinder 2
31213
Input
Register
Integer
0 -
6553
5
5
min
Read
Reads operating time
for cylinder 2 (NHTC-
150 and NHTC-200
only). Each number is
equivalent to 5 minutes
of operation.
Time in hours = (Value x
5)/60
UnitStatus
Displays
status
warnings
31385
Input
Register
Integer 0-99 - Read
11 = Security loop open
19 = Cylinder spent
warning
If status 19, unit will
have yellow service light
on and will continue to
run for 72hrs
CylSpent
Displays
cylinder end
of life fault
30378
Input
Register
Integer 0-99 - Read
Unit will not run until
cylinder is replaced
19 = Cylinder spend
fault
SysTotalDem
Displays the
total demand
on system
(sum both
cylinders)
30251
Input
Register
Integer
0 -
100
% Read
Sum of Steam Output
Cyl-1 and Cyl-2 in
percentage
20 |Modbus Installation
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 51 52

Comments to this Manuals

No comments