27 | SAM-e Installation
Mini SAM-e Pressurized without External Separator
• Max steam pressure of 15 psig when no separator is used.
• Steam components in grey provided by Nortec.
• Tap steam from top of pressurize steam main to avoid excess condensate.
• Condensate from separator to be returned to pressurized condensate main.
• Condensate from SAM-e to be returned to atmospheric floor drain.
When pressurized steam enters SAM-e, pressure drops down to almost atmospheric pressure.
Therefore, it must be drained atmospherically, and the use of a condensate pump (rated for 212ºF)
must be used to raise condensate to a higher elevation.
Strainer
Manual Shut-Off
Valve (By Others)
Steam Main
1” Air Gap
Drain
Steam from top of main
6” min.
Return to non-pressurized
condensate return main
Pressurized condensate
return main